Appendix A Technical Specifications
Appendix A - Technical Specifications of the SAMMS-MV Device
M
M o
o tto
o rr  C
C o
o n
nttrro
o ll  S
S p
p e
ec
c iiffiic
c a
attiio
o n
ns
s
Inputs
Six pushbuttons
Four remote inputs
Outputs
SAMMS-MVX:
Three coil drivers
Three light bars
One programmable alarm contact
SAMMS-MVE:
One coil driver
Two light bars
Diagnostic LEDs
*  Current unbalance
*  Impending trip
*  Overload trip
*  External trip
*  Incomplete sequence
*  Ground fault
*  CPU fault
*  Ready
*  Light bar flashes (timer timing)
*  Impending trip LED flashes (motor temperature warning)
*  Overload trip LED flashes (start inhibit)
*  CPU LED ON (momentary loss of voltage)
Current Ranges:
18 - 72A
60 - 240A
192 - 400A
320 - 720A
Overload Relay Size:
H3A
H3B
H3C
H6
P
P e
e rrm
m iis
ss
s iib
b lle
e  
  C
CT
T   R
R a
attiio
os
s
5A secondary CT ratios (functions
F4A & F5A)
Overload Relay Size
H3A
H3B
H3C
H6
Permissible CT Ratios
30:5, 40:5, 50:5, 75:5, 100:5
100:5, 150:5, 200:5, 250:5, 300:5, 400:5
300:5, 400:5, 500:5, 600:5
500:5, 600:5, 800:5, 1000:5