Overload classes
Overload classes 2 through 23 with one second increments.
Trip Characteristics
Tripping time at 6 x I    = 95% of the overload class (±5%).
Tripping time at 1.5 x I    within two minutes for warm conditions for all classes.
Tripping threshold
(1.1 ± 0.05) x I    for motors with 1.00 service factor, and
(1.2 ± 0.05) x I    for motors with 1.15 service factor.
Tripping time
20 minutes @1.15 x I    for motors with service factor 1.
Mechanical jam protection
SAMMS-MVX only
Sudden increase of the motor running current.  Pick-up current adjustable from 120 to
400% in increments of 5% of I   . Pick-up time 360 msec.
Default values: 200% I    .
Loss of load protection
SAMMS-MVX only
Sudden decrease of motor running current.  Pick-up current adjustable form 20 to 95% in
increments of 5% of I   .  Pick-up time 360 msec.
Default values: 50% I   .
Process current warning
SAMMS-MVX only
Settings from 0 to 100% of I   .
Accuracy
± 5% of overload trip curve values.
± 2% repeat accuracy.
Phase unbalance protection
Response time after 1 second
Shifted trip threshold value to 0.9 x I    at 40% phase unbalance.
Equipment ground fault protection
Response time after 1.4 seconds.
Pick-up time: 360 msec.
Pick-up current:
Overload Relay Size    Pick-up Current     Default
    H3A                            7A- I                10A
    H3B                            7A- I                10A
    H3C                            7A- I                10A
    H6                               7A- I                20A
Rotor protection
Cold stall time adjustable from 5 to 100 seconds in increments of 1 second. If cold stall
time is not known, default value shall be according to the type of motor used.
Motor Type                                        Cold Stall Time
Open Drip Proof (ODP)                         10 Seconds
Totally Enclosed Fan Cooled (EFC)        20 Seconds
Ambient temperature
Motor ambient temperature adjustable 0 - 70°C in increments of 5°C.
Default value: 40°C.