Siemens eWON4002 Manual De Usuario

Descargar
Página de 38
page 17 of 35
ver 2.04
 5.6 Digital Outputs
There are 3 Digital Outputs: 1 open collector and 2 relays.
 5.6.1 Open collector Digital Output
The open collector output is located on the Input/Output connector, which stands beside the power supply 
connector.
This Digital Output is activated by an open collector transistor driven by an optocoupler. The maximum current flow 
into this transistor has a characteristic above the value specified in the eWON®, in order to cope with the switching 
power losses. The transistor used is of open collector type with pre drive. This means the relay power supply has to 
be supplied from an external source to the pre drive electronics.
The diagram below shows the external wiring needed for correct operation of the Digital Output. A relay has been 
chosen for this sample application but any load within the specifications can be used instead.
Warning: note that this is a sink only output to ground (the transistor acts like a switch to ground).
Figure 11: Digital output: wiring diagram
Specification
Value
Type of output
Open collector
Max current (external source)
200mA @ 30 VDC
Isolation
3,5 kV
Pinout connector
See label and appendix (
Table 15: Open collector Digital Output specification