 5.6.2 Relays
The 2 relays are on the RL1-RL2 connector.
 5.7 Analog Inputs
There are 6 Analog Inputs available, 4 of them are configurable in 0-10V or 0-20mA, the 2 others are PT100 Inputs.
 5.7.1 Configurable standard Analog Inputs (AI1 - AI4)
The selection of Analog Input range is done by a dip switch located above the Analog Inputs connector (rear switch):
Figure 12: Rear switch panel and label (the label stands on the left side from the eWON
®
)
• To configure a channel to voltage input, place the matching switch to OFF.
• To configure a channel to current input, place the matching switch to ON.
Specification
Value
Number of outputs
2
Type of output
SPST NO relays (Single Pole, Single Throw, 
Normally Open)
Input voltage max
24 VDC/24 VAC
Max current (external source)
1A
Isolation
1 kV
Pinout connector
See label and appendix (