 6 Communicating with the eWON®
 6.1 By Ethernet
1 ) Plug one of the Ethernet cables [see appendix (
 and 
)] between your eWON® and either your PC (crossed cable) or onto your network (straight 
cable).
2 ) Configure your Internet browser connection, in order not to use a proxy server (please have a look at your 
browser help file)..
With a direct connection between PC and eWON®, TCP/IP settings have to be with fixed IP addresses and 
hence cannot have DHCP enabled (automatic IP address allocation by host).
3 ) Launch your Internet Browser on your PC.
4 ) Type the eWON® TCP/IP address on the address edit control of your Internet Browser (10.0.0.53 is the factory 
default by Ethernet).
5 ) The eWON® returns its login web page. If not -404 Error, server not found-, redo the procedure from the 
beginning and check whether you did not forget anything.
6 ) Introduce the default login parameters that are: 
• User Name: <adm>
• Password: <adm>
7 ) You can now access the different web pages of the eWON® and, among others, configure your connection 
parameters by selecting the following options in the menu of the home page:
• To configure the Ethernet IP address:
<Configuration>, <System Setup>, <Communication>, <Ethernet>
• To configure the PPP IP address:
<Configuration>, <System Setup>, <Communication>, <DialUp (PPP)>
 6.2 By phone line or GSM
 6.2.1 Under Windows 98, NT and 2000
1 ) Open the root folder Dial-up Networking.
2 ) Click on the icon Make new connection.
3 ) Give a name to this connection.
4 ) Select a local modem from the list and click Next.
5 ) Introduce the phone number and the login <adm> and password <adm> of your eWON® (or the login/
password you have created) and click Next.
6 ) Click Finish.
7 ) A new icon has been created in the Dialup Networking folder.
8 ) Open the connection wizard by double clicking on this icon and introduce the login/password for PPP 
authentication which are the same than those for the eWON® Web site access (<adm> / <adm> by default). 
Make the connection and wait until the modems are synchronized (MDM led on the front panel is active) and 
that your authentication login has been accepted.
9 ) Launch your Internet Browser on your PC.
10 ) Types the eWON® TCP/IP address on the address edit control of your Internet Browser (202.0.0.240 is the 
eWON® but you could have modified, in this case use the new address).
11 ) The eWON® should display its login web page. If not -404 Error, server not found-, redo the procedure from 
the beginning and check whether you did not forget anything.
12 ) Unless you have changed them, introduce the default Web site access login parameters that are:
• User Name: <adm>
• Password: <adm>
13 ) You can now access the different Web pages of the eWON® and, among others, configure your connection 
parameters by selecting the following options in the menu of the home page: