Programming and Operating Concepts 
 
Video Recorder – User Manual 
50
Table 3-3 Function Block Types 
Function block 
name 
Type 
Maximum 
available* 
Purpose 
Alarm 
AL 
96 
Causes alarms under specified conditions. 
Analog Input 
AI 
48 
Interfaces with measuring input hardware (thermocouple, 
RTD, mA, volts). 
Analog Output 
AO 
Interfaces with analog output hardware (current output 
(CAT)) or with output relay hardware (time proportion 
(DAT)). 
Calculated Value 
CV 
96 
Performs various calculations on specified parameters. 
Constant 
CN 
32 
Outputs a number or an analog parameter value. 
Discrete Input 
DI 
36 
Interfaces with discrete input hardware (dry contact 
closure). 
Discrete Output 
DO 
36 
Interfaces with output relay hardware (AC relay, DC 
relay, mechanical relay, open collector output). 
Loop 
LP 
PID or ON/OFF control with various outputs. 
Setpoint Profiler 
SP 
Generates a time-varying setpoint for a loop’s Setpoint 
#2
System 
SY 
Outputs discrete status of alarms, data storage, and 
diagnostics; outputs analog value of reference junction 
temperature. This function block is not programmable; its 
outputs are produced automatically. 
Totalizer 
TL 
48 
Outputs accumulated total over time. 
* Depends on options ordered. 
 
 
 
 
Why use function blocks? 
Function blocks give you configuration flexibility.  For instance, the instrument does not have a dedicated 
relay that is activated during an alarm; instead, you can program any of several Alarm function blocks to 
control any relay.  Also, there is not a specific input for your process variable; any of several Analog Input 
function blocks can be programmed to be your process variable.  In general, function blocks let you 
connect the output parameter of any function block to the input parameter of any function block.