Programming and Operating Concepts 
 
Video Recorder – User Manual 
 
51
3.10  Components of function blocks 
The three components of a function block are: 
Input parameter(s) 
Function block parameter(s) 
Output parameter(s). 
Figure 3-7 shows the function block Alarm #1’s components. 
In put paramete r
Outp ut paramet ers
AL  1   OS (Alarm s ta te )
AL  1  S 2 (C omp are point   o f
 De vi ati on alarm o nly )
AL 1  P V (Value of  a larm' s IN PUT)
ALARM ACTION ( Select  H igh,  L ow, Dev , LRat e, H Rate )
IN  D ECI MAL POS ( Selec t input  d ecima l pos it ion)
IN PUT (Selec t  OFF , Numb er,  or PARM)
SETPOI N T (Select OFF, Numb er or PARM)
COMPARE P OINT (Selec t  OFF , N umber, or P ARM)
HY STER ESIS  ( Select OFF or Numb er)
DE LAY TIME (Select  OFF  or N umber)
Al a rm 1  F u nc ti on Bl o c k
Functi on block  paramete r
Functi on block  paramete r
Functi on block  paramete r
Functi on block  paramete r
In put paramete r
In put paramete r
 
Figure 3-7   Alarm 1 Function Block Components 
 
Input parameter 
A function block's input parameter can be configured to be OFF, a number, or it can receive its data from 
outside the block from another block's output codes.  These output codes are shown in 
 
Table 3-4.  That is, an input parameter is any menu item that can be programmed as (connected to) one 
of these output codes. These output codes are grouped under the menu choice PARM.  When you are 
programming a function block and one of your choices is PARM, you know you are programming an 
input parameter.  See Figure 3-7. 
For example, suppose you are programming an alarm function block.  One of the alarm’s menu items is 
INPUT, which specifies which point will be monitored for an alarm condition.  One of the choices for the 
INPUT is PARM, which lets you connect the INPUT to one of the output codes in Table 3-4.  Therefore, 
the INPUT is an input parameter because it receives its data from another function block. 
Some function blocks can have multiple input parameters.  For example, an Alarm function block has an 
INPUT and a SETPOINT, both of which can be connected to other function blocks. 
Discrete Input function blocks have no input parameters; that is, they have no inputs that can be 
connected to another block’s output codes.