SECTION 5: MAJOR COMPONENTS 
FIGURE 13: Major Component Descriptions
Burner with Tube Gasket
Must be installed with the 
flame observation window 
facing down.
Reflector (Aluminum or 
Stainless Steel)
Alternate overlap as shown on 
overview and on Page 16, 
Figure 16
. Minimum overlap is 
6'' (16 cm).
Tube and Reflector Hanger 
with Clamp Package
Position this hanger no more 
than 4” (10 cm) away from the 
burner.
Coupling Assembly with Lock
Reflector End Cap
Punch out center section to 
accommodate tube.
Tube and Reflector Hanger
Suspend system from these 
hangers.
Flex Gas Line with 
Shut Off Cock
Tube
Hot rolled or heat treated 
aluminized tube supplied in 
10' (3 m) lengths.
Burner Tube
Supplied in 10' (3 m) lengths. 
Burner tube is always the first 
tube after the burner.
Reflector Support Strap & 
Wire Form
Turbulator
Turbulator must be installed in the 
last standard section of tube. 
Turbulator is not required on the 
BH-125/150/175/200. For 
installation, see Page 20, Step 6.4
Vent Adapter