Roberts Gorden BH-150 Manuel D’Utilisation
BH-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
12
Additional tubing length may be added to heater. Tubing must be heat-treated, aluminized or porcelain
coated. Any additional tubing lengths are considered as vent length for length determination. Maximum
venting length for minimum heater length is 45' (13.7 m) total.
coated. Any additional tubing lengths are considered as vent length for length determination. Maximum
venting length for minimum heater length is 45' (13.7 m) total.
Table 3: BH-Series Component Package Guide
Model
Tubing Length
Core Packages
Minimum
Standard
Aluminized
BH-40
10' (3 m)
-
CP10ALUM
BH-60
20' (6 m)
CP20HRS
CP20ALUM
BH-80
20' (6 m)
CP20HRS
CP20ALUM
BH-100
30' (9 m)
CP30HRS
CP30ALUM
BH-115
30' (9 m)
CP30HRS
CP30ALUM
BH-125
40' (12 m)
CP40HRS
CP40ALUM
BH-140
40' (12 m)
CP40HRS
CP40ALUM
BH-150
50' (15 m)
CP30HRS + EXP20HRS
CP30ALUM + EXP20ALUM
BH-175
50' (15 m)
CP30HRS + EXP20HRS
CP30ALUM + EXP20ALUM
BH-200
60' (18 m)
CP30HRS + EXP30HRS
CP30ALUM + EXP30ALUM