Sterling 350-2100 CFM Manuel D’Utilisation

Page de 58
350-2100 cfm Dryers 
Chapter 6: Maintenance 
46 of 58 
 
 
 
 
Figure 8:  Process Temperature Control Error Messages 
 
Message 
Cause 
Control Output 
Alarm Output 
 
 
With output unit 
other than current 
output unit 
With current output unit 
 
 
 
Input temperature 
has risen beyond the 
upper limit of the 
temperature range 
by more than 20
°C 
[68
°F] 
c
 
OFF during 
reverse (heating) 
action, ON during 
normal cooling 
action. 
4 mA during reverse 
(heating) action, 20 mA 
during normal (cooling) 
action. 
 
Issues alarm 
outputs in 
accordance with the 
set alarm mode.  
 
 
Input temperature 
has fallen below the 
lower limit of the 
temperature range 
by more than 20
°C 
[68
°F] 
 
ON during reverse 
(heating) action, 
OFF during 
normal (cooling) 
action. 
20 mA during reverse 
(heating) action, 4 mA 
during normal (cooling) 
action. 
 
Issues alarm 
outputs in 
accordance with the 
set alarm mode.  
 
 
The thermocouple 
has burned out or 
the short circuit bar 
has been removed. 
The platinum RTD 
has burned out or A 
and B have been 
short circuited. 
 
 
 
OFF 
 
 
 
Approximately 1 mA 
 
Issues alarm 
outputs in 
accordance with the 
set alarm mode. 
Proportional alarm 
output is OFF 
 
 
 
 
[FLASHES] 
Memory failure 
(E111) or analog to 
digital converter 
failure (E333) has 
occurred. 
Temperature 
controller must be 
repaired if recovery 
is not made by 
turning power off 
once and on again. 
 
 
 
 
 
OFF 
 
 
 
 
 
Approximately 1 mA 
 
 
 
 
 
OFF 
 
c
 When a type J thermocouple is used, this error message is not displayed until the temperature has risen above the normal operating 
temperature operating range by more than 70
°C [158°F]. 
 
d
 When a platinum RTD sensor is used, this message is displayed when the temperature has fallen to -99.9
°C [-147.82°F].