Sterling 350-2100 CFM Manuel D’Utilisation

Page de 58
350-2100 cfm Dryers 
Chapter 6: Maintenance 
47 of 58 
 
Figure 9:  Regeneration Monitor Signal Processor Error Messages 
 
 
Item 
 
Condition 
 
Error  
Output Status 
 
Corrective  
  
Message 
Compara-
tive 
Outputs 
BCD 
Output 
Linear 
Output 
Commun-
ications 
Action 
 
 
 
 
 
Device 
Failure 
CPU RAM 
error, 
external 
memory 
error, 
memory 
data error. 
 
 
 
 
 
 
OFF 
 
 
 
OFF 
 
 
 
OFF 
 
 
 
OFF 
 
Turn the power OFF 
and then ON again 
once. If the error 
persists, call Service. 
 
 
 
Corrupted 
Data 
 
 
 
 
 
 
 
OFF 
 
 
 
OFF 
 
 
 
OFF 
 
 
 
OFF 
Turn the power OFF 
and then ON again 
once. If the error 
persists, press the 
mode key and set all 
parameters again. 
 
 
 
 
Sensor 
Error 
Breakage or 
short circuit of 
sensor. When 
the 
thermocouple 
is used, 
terminals 11 
and 13 are 
not short 
circuited. 
 
 
 
 
 
 
 
 
 
 
OFF 
 
 
 
 
 
OFF 
 
 
 
 
 
OFF 
 
 
 
 
 
 
OFF 
 
 
 
 
Check sensors for 
breakage, short 
circuiting, or incorrect 
wiring. 
 
Overflow, 
Underflow 
Input value 
or display 
value 
outside 
range.  
 
Display 
Blinks 
 
 
Continues 
 
Continues 
OVER 
ON 
 
 
Continues 
 
Continues 
OVER ON 
 
Keep the input value 
and display value 
within the range. 
 
 
Output 
Type 
Change 
 
When 
output type 
has 
changed. 
 
 
 
 
 
 
OFF 
 
 
 
OFF 
 
 
 
OFF 
 
 
 
OFF 
Check the output type. 
If correct, press the 
mode key. This erases 
the set the parameters, 
so re-enter them. If the 
problem persists, call  
Service. 
Output 
Type Error 
 
Output type 
other than 
specified. 
 
 
 
 
 
OFF 
 
 
OFF 
 
 
OFF 
 
 
OFF 
Turn the power OFF 
and then ON again 
once. If the error 
persists, call Service. 
Input 
Specifi-
cation 
Error 
Input type 
other than 
specified. 
 
 
 
 
 
OFF 
 
 
OFF 
 
 
OFF 
 
 
OFF 
Turn the power OFF 
and then ON again 
once. If the error 
persists, call Service.