Measure 
This 
Distance
Figure 5 - Measuring Heat Resistant Material
Heat resistant material (minimum requirements) with no wooden mantel or other combustible projection: 
To install the gas logs into a fireplace with no wooden mantel, shelf or other combustible projection above the 
fireplace opening, measure the heat resistant material height, per Figure 5, then see TABLE A.
Heat resistant materials such as slate and marble must 
be at least 1/2” thick. Sheet metal should not be 
installed onto combustible material.
IMPORTANT: 
If you cannot meet these minimum clearances you must operate the heater with chimney flue 
damper open. Refer to “Installing Vented Applications” found on Page 18.
TABLE A - Heat Resistant Material Requirements with no Mantel or Combustible Projection
CLEARANCES and HEIGHT REQUIREMENTS
 
Heat Resistant 
 
Material 
Requirements for Safe Installation
  Measurement 
MJ27
  12" or more 
Hood not required
  8" to less than 12" 
Extend heat resistant material to 12" 
OR install hood.  
   
 
Refer to Figure 5
  Less than 8" 
Extend heat resistant material to 8" 
AND install hood.  
   
 
Refer to Figure 5. 
OR, extend heat resistant material  
   
 
to a height of at least 12"