PROBLEM P
OSSIBLE CAUSE 
REMARK 
No power 
Check the voltage. Call an electrician if not 
within correct limits of +/- 10% of nominal 
voltage rating required. 
Wiring 
Check terminals. Repair and correct if loose. 
Temperature setting 
Check and adjust the thermostat. 
Main switch setting 
Check and adjust the main switch setting. 
Reversing valve wire 
Check the resistance of reversing valve wire. 
Replace the wire if short, open or damaged.   
No cooling or 
heating. 
Reversing valve 
If the reversing valve is blocked, the heating 
mode will not operate. Replace the reversing 
valve after checking the reason for failure. 
Voltage 
Check voltage. Call Supply Authority if not 
within limits of +/- 10% of nominal voltage 
rating required. 
Wiring 
Check the wire connections, if loose, repair 
or replace the terminal. If wires are off, 
refer to wiring diagram for identification, 
and replace. Check wire locations. If not 
per wiring diagram, correct. 
Main switch failure 
Check and replace the main switch if failed.
Capacitor (Discharge 
capacitor before testing) 
Check the capacitor.                                         
Replace if not within +/-10% of 
manufacturer’s rating. Replace if shorted, 
open, or damaged.   
Thermostat 
Check the thermostat setting if not at the 
coolest (in cooling mode) or the warmest (in 
heating mode). Try adjusting these settings. 
Compressor will not 
run while fan motor 
runs. 
Compressor 
Check the compressor for open circuit or 
ground. If open or grounded, replace the 
compressor. 
Excessive noise. 
Copper tubing 
If copper tubing is rubbing against the cabinet 
and vibrating while operating, remove the 
cabinet and carefully rearrange tubing to not 
contact cabinet, compressor, shroud and barrier.
Power supply 
The input power supply voltage is too low or 
not within +/- 10% of nominal voltage rating 
required. Call an electrician if not within limits.
The unit starts and 
stops frequently. 
Outdoor temperature 
When the outdoor temperature is too high, 
the compressor will go into a protection 
mode or 3 minute time delay. 
 
Service Manual
Room Air Conditioner with R-410A