board will alarm on ignition failures, compressor lock-
outs and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent 
nuisance trouble calls, the control board uses a “three 
times, you’re out” philosophy.  The high and low-pres-
sure switches and the freezestats must trip three times 
within two hours before the unit control board will lock 
out the associated compressor.
On Board Diagnostics - Each alarm will energize a 
trouble light on the thermostat, if so equipped, and 
flash an alarm code on the control board LED.  Each 
high and low-pressure switch alarm as well as each 
freezestat alarm has its own flash code.  The control 
board saves the five most recent alarms in memory, 
and these alarms can be reviewed at any time. 
Alarms and programmed values are retained through 
the loss of power.
• Reliable – From the beginning – All units undergo 
computer automated testing before they leave the factory. 
Units are tested for refrigerant charge and pressure, unit 
amperage, and 100% functionality. For the long term – All 
Predator
®
 units are painted with a long lasting, powder 
paint that stands up over the life of the unit. The paint 
used has been proven by a 1000 hour salt spray test.
• Flexible Placement – All models and configurations 
share the same cabinet/footprint and thus the same roof 
curb. You have the flexibility to set one curb and choose 
the correct tonnage size and heating option after the 
internal loads have been determined.
To further simplify planning and installation, Predator
®
  
cabinets are designed to fit your roof. With the optional 
roof curb, the unit ductwork is designed to fit around 24” 
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or 
the rear of the unit. Additionally, the drain pan can be 
fitted to drain through the roof curb. As it is sometimes 
difficult to have a level installation, the drain pan features 
a generous slope to ensure proper drainage.
• Full Perimeter Base Rails – The permanently attached 
base rails provide a solid foundation for the entire unit and 
protect the unit during shipment. The rails offer forklift 
access from 3 sides, and rigging holes are available so that 
an overhead crane can be used to place the units on a roof.
• Easy Installation – Gas and electric utility knockouts are 
supplied in the unit underside as well as the side of the unit. 
A clearly identified location is provided to mount a field 
supplied electrical disconnect switch. Utility connections can 
be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
• Wide Range of Indoor Airflows – All indoor fan motors 
are belt-drive type providing maximum flexibility to handle 
most airflow requirements. For high static applications, 
factory installed alternate indoor fan motors are available. 
With the optional indoor fan motor, all units can supply 
nominal airflow at a minimum of 1.5” ESP.
A variable air volume (VAV) option using a variable 
frequency drive is available on 6-1/2 through 12-1/2 ton 
models for applications requiring a constant supply duct 
pressure. A differential pressure transducer is used to 
monitor supply duct static pressure while a VAV control 
board provides a speed reference signal to the VFD to 
control the output of the indoor blower motor.
• Warranty - All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater 
elements each carry a 5-year warranty. Aluminized steel 
and stainless steel tubular heat exchangers carry a 10-
year warranty.
Factory Installed Options
YORK
®
 offers several equipment options factory installed, for 
the Predator
®
line.
• Optional Factory Installed Economizers - Predator units 
offer a variety of optional factory installed economizers 
with low leak dampers. The outdoor air enthalpy sensor 
enables economizer operation if the outdoor enthalpy is 
less than the setpoint of the economizer logic module. See 
economizer options section to determine the correct 
economizer for your application.
• Downflow Economizer (With barometric relief) 
The economizer is provided with a single enthalpy input. 
The economizer is 2% low leakage type, and is shipped 
installed and wired. The installer needs only to 
assemble the outdoor air hood, attach the enthalpy 
control to the hood and mount the hood to the unit 
(Hood and control are provided). The economizer has 
spring return, fully modulating damper actuators and is 
capable of introducing up to 100% outdoor air. As the 
outdoor air intake dampers open, the return air dampers 
close. The changeover from mechanical refrigeration to 
economizer operation is regulated by the standard 
single enthalpy input. To meet regulated air standards, 
the economizer control accepts an optional CO
2
 
input 
for
 
demand ventilation. With single enthalpy input, the 
economizer control monitors outdoor air. The dual 
enthalpy kit provides a second input used to monitor the 
return air. With a dual input kit installed, the economizer 
control compares the values of the two enthalpy or 
temperature inputs and positions the dampers to 
provide the maximum efficiency possible.
• Horizontal Economizer (Without barometric relief) 
All features of the downflow economizer exist except you 
must order the duct mount barometric relief separately. 
You must order a 1EH0408 if you are installing a 
power exhaust. You can order a 1RD0411 Barometric 
Relief for horizontal flow economizers only.
• BAS Ready Economizer -(With barometric relief) 
The economizer is provided with an actuator that 
requires a 2-10V DC input from an external source (i.e., 
field installed building automation system controller). 
Power exhaust options are available. The economizer is 
2% low leakage type with spring return and fully 
modulating dampers capable of introducing up to 100% 
outside air. Also include 2” pleated filters. BAS ready