MAINTENANCE 
 
 
 
CRITERIA: 
 
1.   If  a  current  flow  above  5  milli-amperes  is 
observed  or  if  breakdown  occurs,  one  or 
more  of  the  interrupters  has  insufficient 
vacuum and must be replaced. 
 
Exception:  
If the current exceeds 5 milli-
amperes the first time the voltage is brought 
up, reduce the voltage to zero and increase it 
again.    It  may  be  necessary  to  repeat  this 
procedure a few times. 
 
2.   If  the  contactor  fails  to  meet  criteria  1,  then 
repeat  the  test  on  each  pole  separately  to 
identify  the  damaged  interrupter  or 
interrupters. 
 
3.   If  the  voltage  can  be  held  for  1  minute  and 
the  current  flow  does  not  exceed  5  milli-
amperes,  the  interrupter  has  a  sufficient 
vacuum level. 
 
After the test is complete, discharge any residual 
static  charge  from  the  primary  terminals  of  the 
circuit breaker.  
 
If  a  vacuum  checker  or  AC  hi-pot  tester  is  not 
available,  a  DC  hi  potential  test  may  be 
conducted.    If  a  DC  test  is  conducted,  the  test 
voltage must be increased to 14kV DC.  The test 
duration  for  DC  tests  and  the  criteria  for 
acceptance remain the same as for AC tests. 
 
Do not use DC hi-pot 
testers which employ 
unfiltered half-wave 
rectifiers.  The peak 
voltages produced by these 
testers may exceed the 
recommended value of 
14kV.  This can result in the 
production of harmful X-
rays and may invalidate the 
test results. 
 
 
 
 
Figure 12 - Application of Test Voltage for 
Vacuum Check 
 
 
 
 
 
 
 
 
          1 minute 
10kV AC 
(14kV DC) 
 
 
 
Voltage 
 
 
 
  Zero 
 
  10 sec 
 
 
 10 sec 
 
 
 
Time 
    WARNING 