Toshiba HCV-1JBU Manuel D'Instructions

Page de 30
 
MAINTENANCE 
 
Page 23 
 
 
 
ELECTRICAL SERVICE LIFE 
 
The  electrical  service  life  of  the  vacuum 
interrupter is defined by the electrode wear and 
the  number  of  open/close  operations 
(mechanical life). 
 
To  determine  electrode  wear,  measure  the 
distance  between  the  lever  and  washer  in  the 
closed (ON) state, as shown in Figure 13.  This 
dimension  is  called  the  “wipe”.    If  the  1.0mm 
contact  wear  gauge  cannot  be  inserted,  then 
the  end  of  the  service  life  has  been  reached.  
The maximum number of open/close operations 
is 500,000 regardless of the magnitudes of the 
currents  interrupted.    Contact  Toshiba  for 
information  regarding  replacement  of  the 
vacuum interrupters. 
 
The  drive  unit  and  the  closing  coils  also  have 
an electrical service life of 500,000 operations.  
As  a  result,  these  parts  should  be  replaced 
around 500,000 operations. 
 
 
MECHANICAL SERVICE LIFE 
 
The normally energized type has a mechanical 
service  life  of  2.5  million  operations.    The 
mechanical  service  life  of  the  vacuum 
interrupters is 500,000 operations. 
 
For  the  components  listed  in  Table  4, 
replacement or detailed inspection and cleaning 
are recommended after the indicated number of 
operations. 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 13 - Wipe Measurement 
 
 
Table 4 - Recommended Part Replacement 
Intervals 
Part Name 
Number of Operations 
for Replacement 
Vacuum Interrupter  500,000 
Auxiliary Switch 
200,000 
Moveable Core 
Detailed inspection and 
cleaning every 500,000 
operations. 
Stationary Core 
Detailed inspection and 
cleaning every 500,000 
operations. 
Closing Coil 
500,000 
Flexible Conductor  500,000 
 
 
SERVICE LIFE – CAPACITOR SWITCHING 
 
Switching  of  the  capacitor  loads  produces 
severe  conditions  for  contactors,  such  as  high 
frequency  inrush  current  and  phase-to-phase 
recovery  voltage  more  than  twice  the  normal 
voltage. 
 
The  criterion  for  the  maximum  number  of  the 
capacitor current switching operations is shown 
in Figure 14.  The vacuum interrupter should be 
replaced  when  the  number  of  switching 
operations in the graph is reached. 
Figure 14 - Capacitor Switching Life 
1
10
10
100
1000
Switching Current (A)
Switching 
Life 
(ten 
thousand)
 
 
8
20          40     60                    200        400  600 
A
Isolation
Flange