CONNECTING ELECTRIC DRYERS 
(cont.)
Remove 3
1
2
 inches (8.9 cm) of the outer 
covering from the wire. Strip 1 inch (2.5 cm) 
insulation from each wire. Bend the ends of 
the three wires into a hook shape.
1
Remove the terminal block access cover  
on the upper back of the dryer. Install a  
UL-listed strain relief into the power cord 
through-hole; then thread the power cable 
prepared in Step 1 through the strain relief.
2
UL-Listed 
Strain Relief
UL-Listed  
3-Wire  
Power Cord
Terminal 
Block
Attach the two hot leads of the power cord 
to the outer terminal block screws. Attach 
the neutral wire to the center terminal block 
screw. Connect the external ground (if 
required by local codes) to the green ground 
screw. TIGHTEN ALL SCREWS SECURELY. 
Reinstall the terminal block access cover.
3
Ground Screw
Neutral 
(White)
 Hot  
 Black)
Ground Wire
Hot 
(Red)
1"  (2.5 cm)
Three-Wire Connection for Electric Dryers: Direct Wire
•  A 3-wire connection is NOT permitted on new
construction after January 1, 1996. 
•  A UL-listed strain relief is required.
•  Use UL-listed
3-wire #10 AWG-minimum 
copper conductor cable.
•  Allow at least 5 ft. (1.5 m) length to allow for
removal and reinstallation of the dryer. 
w
WARNING: 
•Connect the power cord to the terminal block. Each colored wire should be connected  
to same color screw. Wire color indicated on manual is connected to the same color 
screw in block. Failure to follow these instructions may result in a short or overload.
•Grounding through the neutral conductor is prohibited for: (1) new branch-circuit  
installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local  
codes prohibit grounding through the neutral conductor.
USA ONLY