7-3-3. Only compressor unit does not run.
A. Check setting temperature.
B. Check compressor and electrical parts.
If the unit is turned off during cooling, DO NOT restart it immediately, as this 
can damage it. Wait at least 3 minutes or so before starting it again.
The compressor does not start up immediately even when the MODE selector 
switch is set to COOL or HEAT (It starts operating in about 3 minutes).
This is because rough 3-minute timer is built into the heat pump model in order
to protect the compressor. When operation is started up or restarted, the fan 
operation begins immediately but the compressor starts operating after about
3-minute lag.
Heat pump model
Cooling & electric heating models
Cooling only models
CAUTION
• Check compressor motor                
capacitor.
• Measure resistance of 
compressor motor winding.
NO
YES
YES
 Overload relay is working.
(OLR)
YES
Temperature of compressor 
is abnormally high.
Refrigerant gas shortage.
Charge refrigerant gas (R22).
Rotor may be locked up.
(Only for 115V models)
Check PTC thermistor.
NO
Is room temperature too low ?
Try to lower setting temperature by 
thermostat knob cooler.
COOL mode 
NO
Is room temperature too high ?
Try to raise setting temperature by 
thermostat knob warmer.
HEAT mode  (Only for heat pump model)