Sanyo STB1020C1 Manuel D’Utilisation

Page de 52
7-4. Air conditioner operates, but abnormalities are observed.
7-4-1. Operation does not switch from HEAT to COOL (or COOL to HEAT).
7-4-2. Poor cooling or heating.
7-4-3. Excessive cooling or heating.
NO
• Set temperature is suitable.
Set temperature to higher or 
lower value using thermostat.
Air filter is clogged.
Temperature
difference
is small.
YES
Temperature difference between
suction and discharge air is
large enough (In cooling operation: 
approx. 14 
°
F or more).
Possibility of
gas shortage.
• Measure temperature of suction and 
discharge air of air conditioner.
Charge refrigerant 
gas (R22).
Check for clogging of air filter.
• Fan speed is set to LOW.
Clean filter.
Set fan speed to HIGH.
• Review cooling load estimate, 
if performance of air conditioner is 
normal.
Reduce cooling or heating 
load or replace the air 
conditioner with larger 
capacity.
Check PCB Ass'y .     (Power pack)
OK
• Measure resistance of 4–way valve's 
winding.
(Only for heat pump model)
33