8-1. Measurement of Insulation
Resistance
The insulation is in good condition if the resistance
exceeds 2M
Ω
.
8-1-1. Power Cord and Unit
Clamp the grounding prong of the power plug with a lead
clip of the insulation resistance tester and measure the
resistance by placing a probe on either of the two power
blade. (Fig. 1)
Then, also measure the resistance between the
grounding prong and other power blade. (Fig. 1)
8-1-2. Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric part
from terminal plate, switch, capacitor, etc. Similarly
disconnect the connector. Then measure the insulation
resistance. 
(Figs. 2 to 3)
Refer to Electric Wiring Diagram.
If the probe cannot enter the poles because the hole is
too narrow then use a probe with a thinner pin.
NOTE
Power plug
Ground
Probe
Insulation tester
Fig. 1
Copper
tube or
metallic part
Clip
Insulation 
tester
Probe
Fig. 2
Clip
Insulation 
tester
Probe
Metallic 
part
From fan motor,
compressor and 
other parts
Fig. 3
Fig. 4
8. CHECKING ELECTRICAL COMPONENTS
   The shape of the power plug may differ from that
   of the air conditioner which you are servicing.
NOTE