FMC Corporation - Talstar 80 Manuel D’Utilisation

Page de 122
Proline Promass 80 PROFIBUS PA
Operation
45
5.6.2
Configuring the device address
The address must always be configured for a PROFIBUS PA device. The valid device addresses are 
in the range from 1 to 126. In a PROFIBUS PA network, each address can only be assigned once. If 
an address is not configured correctly, the device is not recognized by the master. All measuring 
devices are delivered from the factory with the address 126 and with software addressing.
Addressing via local operation/operating program 
Addressing via miniature switches
#
Warning! 
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power 
supply is switched off before you remove the cover of the electronics compartment.
1.
Loosen the Allen screw (3 mm) of the securing clamp.
2.
Unscrew cover of the electronics compartment from the transmitter housing.
3.
Remove the local display (if present) by loosening the set screws of the display module.
4.
Set the position of the miniature switches on the I/O board using a sharp pointed object.
5.
Installation is the reverse of the removal procedure.
a0002590
Fig. 30: 
Addressing with the aid of miniature switches on the I/O board
Miniature switches for setting the device address (illustrated: 1 + 16 + 32 = device address 49)
b
Miniature switches for the address mode (method of addressing):
OFF = software addressing via local operation/operating program (factory setting)
ON = hardware addressing via miniature switches
c
Miniature switches not assigned
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
16
1
3
32
2
4
64
3
4
1
2
b
OFF ON
1
1
2
2
4
3
8
4
a
OFF ON
c
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O