Delta Tau GEO BRICK DRIVE Manuel D’Utilisation

Page de 294
 Geo Brick Drive User Manual 
Motor Setup 
 167 
AC/DC Brushless (Rotary/Linear) Motor Setup 
Before you start 
 
At this point of the setup process it is assumed that the encoder has been wired and configured 
correctly in the Encoder Feedback section. And that moving the motor/encoder shaft by hand 
shows encoder counts in the position window. 
 
Parameters with comments ending with -User Input require the user to enter information 
pertaining to their system/hardware. 
 
Downloading and using the suggested M-variables is highly recommended.   
 
Description of the setup parameters can be found in the 
 
Commutation Angle, Current Mask: Ixx72, Ixx84 
I172,8,100=1365 
; Motors 1-8 Commutation phase angle (Geo Brick Drive specific)  
I184,8,100=$FFF000 
; Motors 1-8 Current-Loop Feedback Mask Word (Geo Brick Drive specific) 
  
 
PWM Scale Factor: Ixx66 
If Motor Rated Voltage > Bus Voltage: 
I166=1.10*I7000 
; Motor #1 PWM Scale Factor. Set to 10% above PWM Count. 
I266=I166 I366=I166 I466=I166 I566=I166 
; Assuming same motor(s) as motor #1  
I666=I166 I766=I166 I866=I166  
 
; Assuming same motor(s) as motor #1 
 
If Bus Voltage > Motor Rated Voltage: 
Ixx66  acts  as a  voltage  limiter.  In  order  to  obtain  full  voltage  output  it  is  set  to  about  10%  over  PWM 
count divided by DC Bus/Motor voltage ratio. For example: 
#define DCBusInput 
325 
; DC Bus Voltage [VDC] = 1.414* 230 VAC -User Input  
 
#define Mtr1Voltage 
156 
; Motor 1 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr2Voltage 
156 
; Motor 2 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr3Voltage 
156 
; Motor 3 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr4Voltage 
156 
; Motor 4 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr5Voltage 
156 
; Motor 5 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr6Voltage 
156 
; Motor 6 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr7Voltage 
156 
; Motor 7 Rated Voltage [VDC], 110 VAC Motor -User Input 
#define Mtr8Voltage 
156 
; Motor 8 Rated Voltage [VDC], 110 VAC Motor -User Input 
 
I166=1.10*I7000*Mtr1Voltage/DCBusInput 
; Motor 1 PWM Scale Factor 
I266=1.10*I7000*Mtr2Voltage/DCBusInput 
; Motor 2 PWM Scale Factor 
I366=1.10*I7000*Mtr3Voltage/DCBusInput 
; Motor 3 PWM Scale Factor 
I466=1.10*I7000*Mtr4Voltage/DCBusInput 
; Motor 4 PWM Scale Factor 
I566=1.10*I7000*Mtr5Voltage/DCBusInput 
; Motor 5 PWM Scale Factor 
I666=1.10*I7000*Mtr6Voltage/DCBusInput 
; Motor 6 PWM Scale Factor 
I766=1.10*I7000*Mtr7Voltage/DCBusInput 
; Motor 7 PWM Scale Factor 
I866=1.10*I7000*Mtr8Voltage/DCBusInput 
; Motor 8 PWM Scale Factor 
 
Current Feedback Address: Ixx82 
I182=$078006 
 
; Motor 1 Current Feedback Address  
I282=$07800E 
 
; Motor 2 Current Feedback Address 
I382=$078016 
 
; Motor 3 Current Feedback Address 
I482=$07801E 
 
; Motor 4 Current Feedback Address 
I582=$078106 
 
; Motor 5 Current Feedback Address 
I682=$07810E 
 
; Motor 6 Current Feedback Address 
I782=$078116 
 
; Motor 7 Current Feedback Address 
I882=$07811E 
 
; Motor 8 Current Feedback Address