Recommended Main Bus Power Wiring/Protection 
 
 
Caution 
Main bus power lines should run in a separate duct (at least 12” or 30 
cm  away)  from  and  should  never  be  bundled  with  the  I/O  signal, 
communication, or encoder cables.   
 
Grounding, Bonding 
System grounding is crucial for proper performance of the Geo Brick Drive.  Panel wiring requires that a 
central  earth-ground  (also  known  as  ground  bus  bar)  location  be  installed  at  one  part  of  the  panel.  The 
ground  bus  bar  is  usually  a  copper  plate  directly  bonded  to  the  back  panel.  This  electrical  ground 
connection allows for each device within the enclosure to have a separate wire brought back to the central 
earth-ground. 
 
 
Implement a star point ground connection scheme; so that each device wired to earth ground 
has its own conductor brought directly back to the central earth ground plate (bus bar). 
 
 
Use  an  unpainted  back  panel.  This  allows  a  wide  area  of  contact  for  all  metallic  surfaces, 
reducing frequency impedances. 
 
 
Use a heavy gauge ground earth conductors made up of many strands of fine conducts.   
 
 
The Geo Brick Drive  is brought to the  earth-ground via one  or two  wire(s) connected to the 
M4  mounting  stud(s)  through  a  heavy  gauge  multi-strand  conductor  to  the  central  earth-
ground.