Installation  (for qualified installers only)
15
© Travis Industries
4040830
100-01143
Vent Requirements
 
The  gas  appliance  and  vent  system  must  be  vented  directly  to  the  outside  of  the  building,  and
never  be  attached  to  a  chimney  serving  a  separate  solid  fuel  or  gas-burning  appliance.    Each
direct vent gas appliance must use it's own separate vent system.
Vent Clearances
 
The  vent  must  maintain  the  required  clearance  to  combustible  materials  to  prevent  a  fire.    Do
not  fill  air  spaces  with  insulation.
Before First Firestop
After First Firestop
Front
1/2"
  0"
Sides
0"
0"
Above
2"
2"
Below  Horizontal  Section
1"
1"
Below  45°  Section
1"
0"
AAAAAA
0" Clearance to the sides 
after the first firestop.
A
A
A
Use a firestop whenever 
passing through a 
ceiling, enclosure or 
floor penetration.
Use a firestop when passing 
through any wall  (WARNING: 
some firestops provide a 1" 
clearance above the vent -- 2" 
is required for this heater).
Min. 2" Clearance 
Above the Vent 
A
A
A
A
A
A
A
A
A
A
A
A
AAAA
1/2" Clearance to the 
front of vent before the 
first firestop.
0" Clearance to the 
side of vent after the 
first firestop.
Altitude Considerations
 
This heater has been tested at altitudes ranging from sea level to 8,000 feet (2,400 M).  In this testing we
have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
 
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult  your  dealer  or  installer  if  you  suspect  an  improperly  adjusted  air  shutter.
Approved Vent
 
Use  Model  GS  Direct  Vent  manufactured  by
Simpson  Dura-Vent  only.  Follow the
installation  instructions  included  with  the
vent.  For the nearest Simpson Dura-Vent
supplier,  call  (800)  835-4429.
 
Always  use  the  high-wind  cap  for  the  type  of
vent  you  are  using.
 
This  fireplace  accepts  8"  diameter  GS
Direct  Vent.    Vent  configurations  with  at
least  12"  of  rise  may  use  6-5/8"  diameter  GS
Direct Vent (use the reducer - part #
98900165).    See  "Approved  Vent
Configurations"  for  further  details  on  vent.
6-5/8" Diameter Vent 
(minimum 12" vertical rise)
Reducer - # 98900165