Avalon Stoves 21 DV Fireplace Manuale Utente
26
Installation (for qualified installers only)
© Travis Industries
4040830
100-01143
Facing Detail –Facing Over 1” Thick (Brick)
WARNING:
Any facing that extends in front of the faceplate on the sides or top must be non-
combustible.
combustible.
NOTE:
A 3/8” gap is required above the face for face installation.
Top View
NOTE: Make sure to leave a 1/8" gap
around the sides of the face and 3/8"
above (for face installation).
around the sides of the face and 3/8"
above (for face installation).
A
A
Fireplace
Face
Drywall
Framing
AAAAA
Non-combustible facing material (brick, stone,
marble, tile) - required if the facing extends in
front of the face on the sides or top.
marble, tile) - required if the facing extends in
front of the face on the sides or top.
3/8"
The facing is brought up
to the wall trim.
to the wall trim.
The side facing should be spaced 1/8"
from the face (3/8” from the stand-offs).
from the face (3/8” from the stand-offs).
Wall Trim
Side View
A
A
A
Fireplace
AAAA
AAAA
NOTE: Make sure to bring the facing up
to the wall trim.
to the wall trim.
In this example brick is used.
1/8"
3-d View
1/4" Nutdriver
Arched Face Thick Facing Template Part #
225-20040
The Arched Face Thick Facing Template is a
separate component that is required when
using an arched face with facing that extends
beyond the face (e.g.: brick, river rock). It
attaches to the top stand-off with the included
screws. The top edge of the template forms an
arch 3/8” above the face, allowing installers to
use it as a guide for facing installation. Leave
the template in place to hide the construction
materials behind the template.
separate component that is required when
using an arched face with facing that extends
beyond the face (e.g.: brick, river rock). It
attaches to the top stand-off with the included
screws. The top edge of the template forms an
arch 3/8” above the face, allowing installers to
use it as a guide for facing installation. Leave
the template in place to hide the construction
materials behind the template.
Arched Face Thick
Facing Template
NOTE: When installed, there must be a minimum 1/8” gap
between the face and facing.
between the face and facing.