Electrical Data
Electrical Data For Outdoor Models
Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv 
Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty.
RLA
(each)
MCC 
(each)
LRA
(each)
Qty
FLA
(each)
FLA
YH-07
208/230-3-60
1
25.0
39
164
2
2.1
0.0
35.5
45
460-3-60
1
12.2
19
100
2
1.2
0.0
17.6
25
575-3-60
1
9.0
14
78
2
0.9
0.0
13.1
20
YH-10
208/230-3-60
2
15.6
24
110
2
3.0
0.0
41.2
50
460-3-60
2
7.8
12
52
2
1.6
0.0
20.8
25
575-3-60
2
5.8
9
39
2
1.4
0.0
15.8
20
YJ-10
208/230-3-60
2
17.3
27
123
2
3.0
0.0
45.0
60
460-3-60
2
9.6
15
70
2
1.6
0.0
24.8
30
575-3-60
2
7.7
12
53
2
1.4
0.0
20.0
25
YH-12
208/230-3-60
2
22.4
35
149
2
3.0
0.0
56.5
70
460-3-60
2
10.6
17
75
2
1.6
0.0
27.1
35
575-3-60
2
7.7
12
54
2
1.4
0.0
20.0
25
YJ-12
208/230-3-60
2
23.1
36
160
2
3.0
0.0
58.0
80
460-3-60
2
12.2
19
87
2
1.6
0.0
30.7
40
575-3-60
2
8.7
14
62
2
1.4
0.0
22.3
30
YH-15
208/230-3-60
2
25.0
39
164
4
2.1
0.0
64.7
80
460-3-60
2
12.2
19
100
4
1.2
0.0
32.2
40
575-3-60
2
9.0
14
78
4
0.9
0.0
24.0
30
YJ-15
208/230-3-60
2
25.0
39
164
4
2.1
0.0
64.7
80
460-3-60
2
12.2
19
100
4
1.2
0.0
32.2
40
575-3-60
2
9.0
14
78
4
0.9
0.0
24.0
30
YH-20
208/230-3-60
2
30.1
47
225
4
3.0
0.0
79.8
100
460-3-60
2
16.7
26
114
4
1.6
0.0
44.0
60
575-3-60
2
12.2
19
80
4
1.4
0.0
32.9
45
YJ-20
208/230-3-60
2
30.1
47
225
4
3.0
0.0
79.8
100
460-3-60
2
16.7
26
114
4
1.6
0.0
44.0
60
575-3-60
2
12.2
19
80
4
1.4
0.0
32.9
45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.