Johnson Controls R-410A Manuale Utente

Pagina di 100
505430-BTG-A-0309
Johnson Controls Unitary Products
73
Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv 
Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty.
RLA
(each)
MCC 
(each)
LRA
(each)
Qty
FLA
(each)
FLA
PH-07
208/230-3-60
1
25.0
39
164
2
2.1
0.0
35.5
45
460-3-60
1
12.2
19
100
2
1.2
0.0
17.6
25
575-3-60
1
9.0
14
78
2
0.9
0.0
13.1
20
PH-10
208/230-3-60
2
15.6
24
110
2
3.0
0.0
41.2
50
460-3-60
2
7.8
12
52
2
1.6
0.0
20.8
25
575-3-60
2
5.8
9
39
2
1.4
0.0
15.8
20
PH-15
208/230-3-60
2
25.0
39
164
4
2.1
0.0
64.7
80
460-3-60
2
12.2
19
100
4
1.2
0.0
32.2
40
575-3-60
2
9.0
14
78
4
0.9
0.0
24.0
30
PJ-15
208/230-3-60
2
25.0
39
164
4
2.1
0.0
64.7
80
460-3-60
2
12.2
19
100
4
1.2
0.0
32.2
40
575-3-60
2
9.0
14
78
4
0.9
0.0
24.0
30
PH-20
208/230-3-60
2
30.1
47
225
4
3.0
0.0
79.8
100
460-3-60
2
16.7
26
114
4
1.6
0.0
44.0
60
575-3-60
2
12.2
19
80
4
1.4
0.0
32.9
45
PJ-20
208/230-3-60
2
30.1
47
225
4
3.0
0.0
79.8
100
460-3-60
2
16.7
26
114
4
1.6
0.0
44.0
60
575-3-60
2
12.2
19
80
4
1.4
0.0
32.9
45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv 
Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty.
RLA
(each)
MCC 
(each)
LRA
(each)
Qty
FLA
(each)
FLA
PH-07
208/230-3-60
1
25.0
39
164
2
2.1
10.0
45.5
60
460-3-60
1
12.2
19
100
2
1.2
5.0
22.6
30
575-3-60
1
9.0
14
78
2
0.9
4.0
17.1
25
PH-10
208/230-3-60
2
15.6
24
110
2
3.0
10.0
51.2
60
460-3-60
2
7.8
12
52
2
1.6
5.0
25.8
30
575-3-60
2
5.8
9
39
2
1.4
4.0
19.8
25
PH-15
208/230-3-60
2
25.0
39
164
4
2.1
10.0
74.7
90
460-3-60
2
12.2
19
100
4
1.2
5.0
37.2
45
575-3-60
2
9.0
14
78
4
0.9
4.0
28.0
35
PJ-15
208/230-3-60
2
25.0
39
164
4
2.1
10.0
74.7
90
460-3-60
2
12.2
19
100
4
1.2
5.0
37.2
45
575-3-60
2
9.0
14
78
4
0.9
4.0
28.0
35
PH-20
208/230-3-60
2
30.1
47
225
4
3.0
10.0
89.8
110
460-3-60
2
16.7
28
114
4
1.6
5.0
49.0
60
575-3-60
2
12.2
19
80
4
1.4
4.0
36.9
45
PJ-20
208/230-3-60
2
30.1
47
225
4
3.0
10.0
89.8
110
460-3-60
2
16.7
26
114
4
1.6
5.0
49.0
60
575-3-60
2
12.2
19
80
4
1.4
4.0
36.9
45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.