Energy Tech Laboratories DSH Manuale Utente

Pagina di 24
JOHNSON CONTROLS
18
FORM 145.32-IOM1 (908)
COMFORT ALERT™ DIAGNOSTICS 
The Comfort Alert diagnostics module is a breakthrough 
innovation  for  troubleshooting  and  protecting  three 
phase  Copeland  Scroll®  compressors.  The  module 
installs  easily  in  the  electrical  box  of  the  condensing 
unit near the compressor contactor.  By monitoring and 
analyzing data from the Copeland Scroll compressor 
and the thermostat demand, the module can accurately 
detect the cause of electrical and system related failures 
and protect the compressor.  A flashing LED indicator 
communicates the ALERT code and guides the service 
technician more quickly and accurately to the root cause 
of a problem. 
This  module  provides  compressor 
protection and will shut down the com-
pressor  when  compressor  damaging   
conditions are detected. 
LED DESCRIPTION
 
POWER LED (Green): indicates voltage is present at 
the power connection of the module. 
ALERT LED (Yellow): communicates an abnormal sys-
tem condition through a unique flash code. The ALERT 
LED will flash a number of times consecutively, pause 
and then repeat the process. The number of consecu-
tive flashes, defined as the Flash Code, correlates to a 
particular abnormal condition. Detailed descriptions of 
specific ALERT Flash Codes are shown in two tables 
attached to this manual. 
TRIP LED (Red): indicates there is a demand signal 
from the thermostat but no current to the compressor 
is detected by the module. The TRIP LED typically indi-
cates the compressor protector is open or may indicate 
missing  supply  power  to  the  compressor. A  flashing 
TRIP LED indicates the anti-short cycle timer is active, 
preventing compressor from starting. 
INTERPRETING THE DIAGNOSTIC LEDS
When an abnormal system condition occurs, the Comfort 
Alert  module  displays  the  appropriate ALERT  and/or 
TRIP LED. The yellow ALERT LED will flash a number of 
times consecutively, pause and then repeat the process. 
To identify a Flash Code number, count the number of 
consecutive flashes. Every time the module powers up, 
the last ALERT Flash Code that occurred prior to shut 
down is displayed for one minute. If the yellow ALERT 
LED is on solid more than 2 amps are conducted through 
the PROT terminal. The contactor coil may be shorted 
or the PROT terminal miswired. 
Some ALERT codes indicate a compressor damaging 
condition and the Comfort Alert module will shut down 
and lock out the compressor. Refer to the tables below 
to identify ALERT codes that result in a lock out.