Status LED 
Status LED Description 
Status LED Troubleshooting Information 
Green “POWER” 
Module has power 
Supply voltage is present at module terminals
1. Compressor protector is open                                                    
2. Condensing unit power disconnect is open 
3. Compressor circuit breaker or fuse(s)  is open
4. Broken supply wires or connector is not making contact            
5. Compressor power wires not routed 
     through Comfort Alert 
6. Compressor contactor has failed open
Red “TRIP” LED 
Flashing
1. Compressor contactor coil shorted. 
2. Electrical load too high for PROT circuit 
    (maximum 1 Amp) 
3. 24 VAC wired directly to PROT terminal 
1. High head pressure 
2. Condenser coil poor air circulation (dirty, 
     blocked, damaged) 
3. Condenser fan is not running 
4. If low pressure switch is open:
    Refer to Code 3 for troubleshooting 
1. If low pressure switch is open:
  a. Low refrigerant charge
  b. Evaporator blower is not running
  c. Evaporator coil is frozen
  d. Faulty metering device
  e. Condenser coil is dirty
   f. Liquid line restriction (?lter drier                         
      blocked if present) 
2. If high pressure switch is open, go to 
    Flash Code 2 information 
3. Intermittent thermostat demand signal 
4. System or control board defective 
Yellow “ALERT” 
Flash Code 3 
Short Cycling 
Compressor is running only 
brie?y LOCKOUT 
Red “TRIP” LED 
On Solid
Thermostat demand signal Y 
is present, but the 
compressor is not running 
Yellow “ALERT” 
Flash Code 2 
System Pressure Trip 
Discharge pressure out of 
limits or compressor over-
loaded (if no high pressure 
switch in system) 
LOCKOUT 
The anti-short cycle timer (3 minutes), in module is preventing compressor restart. 
Module locks out compressor when compressor damaging ALERT codes appear.                                                 
Lockout ALERT codes are noted in the Status LED Description.                                                                                 
During a compressor lock out, 24VAC power must be removed from module to manually reset 
A short circuit or over current 
condition exists on PROT 
terminal.
Yellow "ALERT" 
LED On Solid
briefly
(filter drier