SS38 Direct Vent Gas Stove
VENTING INSTALLATION INFORMATION
W
ARNING
Read all instructions completely and thoroughly before attempting installation. 
Failure to do so could result in serious injury, property damage or loss of life. 
Operation of improperly installed and maintained venting system could result in 
serious injury, property damage or loss of life.
INSTALLATION PRECAUTIONS
Consult  local  building  codes  before  beginning  the 
installation.  The  installer  must  make  sure  to  select  the 
proper vent system for installation. Before installing vent 
kit,  the  installer  must  read  this  stove  manual  and  vent 
kit instructions. 
Only a qualified installer/service person should install vent-
ing system. The installer must follow these safety rules:
  Wear gloves and safety glasses for protection.
•  
Use extreme caution when using ladders or when 
on rooftops.
•  
Be aware of electrical wiring locations in walls and 
ceilings.
The following actions will void the warranty on your vent-
ing system:
•  
Installation of any damaged venting component.
•  
Unauthorized modification of the venting system.
•  
Installation of any component part not manufactured 
or approved by MHSC.
•  
Installation  other  than  permitted  by  these  instruc-
tions. 
NOTICE
Failure to follow these instructions will 
void the warranty.
This stove must be vented to the outside. 
The  venting  system  must  NEVER  be 
attached to a chimney serving a separate 
solid  fuel  burning  appliance.  Each  gas 
appliance must use a separate vent system. 
Do not use common vent systems.
W
ARNING
W
ARNING
Horizontal  sections  of  this  vent  system 
require  a  minimum  clearance  of  2"  from 
the top of the pipe and 1" minimum to the 
sides and bottom. Vertical sections of this 
system require a minimum of 1" clearance 
to combustible materials on all sides of the 
pipe. Only a 1" clearance is required where 
the vent passes through the nearest vertical 
wall. 
INSTALLATION PLANNING
 
There are two basic types of direct-vent installation:
•  
Horizontal Termination
•  
Vertical Termination
It is important to select the proper length of vent pipe for 
the type of termination you choose. It is also important to 
note the wall thickness. 
FOR HORIZONTAL TERMINATION
Select the amount of vertical rise desired. The horizontal 
run  of  venting  must  have  1/4"  rise  for  every  12"  of  run 
towards the termination. 
You may use up to three 90° elbows in this vent configu-
ration. Refer to Horizontal Termination Configurations on 
Page 13.
W
ARNING
Never run the vent pipe level or downward. 
This  may  cause  excessive  temperatures 
which could cause a fire. 
FOR VERTICAL TERMINATION
Measure the distance from the stove flue outlet to the ceil-
ing. Add the ceiling thickness, the vertical rise in an attic or 
second story, and allow for sufficient vent height above the 
roof line. You may use one or two 90° elbows in this vent 
configuration. Refer to Vertical Termination Configurations 
on Page 16.
NOTE: You may use two 45° elbows in place of a 90° elbow. 
You must follow rise to run ratios when using 45° elbows. 
The appliance is approved for use with three 90° elbows 
maximum or a combination of  90° and 45° elbows up to 
a maximum of 270°. 
For two-story applications, firestops are required at each 
floor level. If an offset is needed in the attic, additional pipe 
and elbows will be required.
You may use a chase with a vent termination with exposed 
pipe on the exterior of the house. Refer to Installing Vent 
System in a Chase

It is very important that the venting system maintain its bal-
ance between the combustion air intake and the flue gas 
exhaust.  Certain  limitations  apply  to  vent  configurations 
and must be strictly followed.