Telect MIX 56 Manuale Utente

Pagina di 124
MIX 56 User Manual
4  Software Operation
122188-10 A0
Telect, Inc.
4-51
When test mode “T1/E1 Test on High Speed Line” is selected then you also 
specify:
1.
Which channel of the muxed DS3 signal to insert the test pattern 
on.
2.
Whether to use a framed test signal or not.
3.
What frame format to use if using a framed test signal.
4.
What remote alarm format to use if T1 line and using a framed test 
signal
When test mode “Unframed Test on Low Speed Line” is selected then you 
also specify which low speed channel to do the test on.
To Specify a BER Test
Step
Action
1.
From the Directory screen, press 20 to select “BER Testing”, then 
press enter. The “BER Testing” screen appears:
2.
In the “Mode” field select the mode by pressing the spacebar to tog-
gle between “CBit DS3 Test on High Speed Line”, “Unframed Test 
on Low Speed Line”, or “T1/E1 Test on High Speed Line” and then 
pressing Enter.
MIX 56 by Telect                      MIX 56                 Directory (CTRL+D)
                                                                       Help (?)
                                   BER Testing
                                   -----------
  
                          Mode: T1/E1 Test on High Speed Line
                       Pattern: Disabled
                                                   Receiving Pattern: None
           Low Speed Channel #: 1                Line Type: T1
                 Framed Signal: Yes
                  Frame Format: ESF
                           RAI: FS Bit
                                                     [Apply]