4 Software Operation
122188-10 A0
Telect, Inc.
4-51
When test mode “T1/E1 Test on High Speed Line” is selected then you also
specify:
specify:
1.
Which channel of the muxed DS3 signal to insert the test pattern
on.
on.
2.
Whether to use a framed test signal or not.
3.
What frame format to use if using a framed test signal.
4.
What remote alarm format to use if T1 line and using a framed test
signal
signal
When test mode “Unframed Test on Low Speed Line” is selected then you
also specify which low speed channel to do the test on.
also specify which low speed channel to do the test on.
To Specify a BER Test
Step
Action
1.
From the Directory screen, press 20 to select “BER Testing”, then
press enter. The “BER Testing” screen appears:
press enter. The “BER Testing” screen appears:
2.
In the “Mode” field select the mode by pressing the spacebar to tog-
gle between “CBit DS3 Test on High Speed Line”, “Unframed Test
on Low Speed Line”, or “T1/E1 Test on High Speed Line” and then
pressing Enter.
gle between “CBit DS3 Test on High Speed Line”, “Unframed Test
on Low Speed Line”, or “T1/E1 Test on High Speed Line” and then
pressing Enter.
MIX 56 by Telect MIX 56 Directory (CTRL+D)
Help (?)
BER Testing
-----------
Mode: T1/E1 Test on High Speed Line
Pattern: Disabled
Receiving Pattern: None
Low Speed Channel #: 1 Line Type: T1
Framed Signal: Yes
Frame Format: ESF
RAI: FS Bit
[Apply]