G8000 Series Installation and Operation Manual
Figure 11.7 shows the terminal mounting hole arrangement for the terminal buss strips for the 500 kVA 
UPS units.   
Figure 11.8 shows the arrangement of the terminal buss strips for the 500 kVA UPS.  The buss strips are 
located inside at the top of the unit. The dashed line on terminals 1–13 indicates the side view of the bolt 
holes. Use 1/2 inch bolts to attach the lugs.
For UPS’ equipped with buss strip terminals for the A/C INPUT, BYPASS INPUT, A/C OUTPUT and 
BATTERY connections, Toshiba recommends using the compression lugs listed in Table 11.3, or their 
equivalent, for cable terminations to be mounted on the bus strips.
3-Phase AC Power Lugs
4 in. (102 mm)
1.75 in.  
(44.5 mm)
0.875 in.  
(22 mm)
1.75 in.  
(44.5 mm) 
6 x 0.5625 in. Dia.  
(14.3 mm)
0.875 in.  
(22 mm)
0.75 in.  
(19 mm)
5.5 in. (140 mm)
1.75 in.  
(44.5 mm)
1.75 in.  
(44.5 mm)
0.875 in.  
(22 mm)
1.75 in.  
(44.5 mm) 
6 x 0.5625 in. Dia.  
(14.3 mm)
0.875 in.  
(22 mm)
0.75 in.  
(19 mm)
3-Phase Neutral and 
Battery (DC)  Power Lugs
FIGURE 11.7 - TERMINAL BUSS DETAILS FOR 500KVA UPS
FIGURE 11.8 - TERMINAL BUSS ARRANGEMENT FOR 500 KVA UPS
G8000 500KVA - INPUT SECTION
G8000 500KVA - OUTPUT SECTION
AC INPUT
U
1
2
V
3
W
BYPASS INPUT
7
N
U
4
5
V
6
W
BATTERY
13
14
+
U
9
10
V
11
W
12
N
AC OUTPUT
GND
8