Toshiba 125 Manuale Utente

Pagina di 120
36
G8000 Series Installation and Operation Manual
See Table 11.5 – Table 11.6 for recommended cable sizes for the 150, 225, 300 and 500 kVA UPS. 
TABLE 11.3  RECOMMENDED CRIMP TYPE COMPRESSION LUGS FOR BUS STRIP TERMINALS
Wire Size
Wire 
Strand 
Class
Recommendation
Crimp tool Required 
Burndy type Y35 or Y46
Vendor
Cat. No.
Color Key
Die Index
1/0
B
Burndy 
Ilsco 
Burndy
YA25 
CRA-1/OL 
YA25-LB
Pink 
Pink 
Black
12 / 348 
12 / 348 
13
2/0
B
Burndy 
Ilsco 
Burndy
YA26 
CRA-2/OL 
YA27-LB
Black 
Black 
Orange
13 
13 
14 / 101
3/0
B
Burndy 
Ilsco 
Burndy
YA-27 
CRB-3/OL 
YA28-LB
Orange 
Orange 
Purple
14 / 101 
14 / 101 
15
4/0
B
Burndy 
Ilsco 
Burndy
YA28 
CRB-4/OL 
YA29-LB
Purple 
Purple 
Yellow
15 
15 
16
300 MCM
B
Burndy 
Ilsco 
Burndy
YA30 
CRA-30OL 
YA32-LB
White 
White 
Red
17 / 298 
17 / 298 
18 / 324
350 MCM
I
Burndy 
Ilsco
YA31L 
CRA-350
Red 
Red
18 
18
600 MCM
I
Burndy 
Ilsco
YA36L 
CRA-600
Green 
Green
22 
22
TABLE 11.4  RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT  
(USE 75 °C Copper Wire)
Recommended external cable sizes for both 75 °C and 90 °C copper wire for minimum battery configurations 
are  listed  in  Table  11.4–11.7.  For  extended  runtime  battery  strings  configurations  consult  with  Toshiba 