Lucent Technologies 555-230-128 Manuale Utente

Pagina di 144
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Compact Modular Cabinets  
555-230-128  
Issue 3
May 1998
Install and Cable the Cabinets 
Page 1-17
AC Power and Ground 
1
CMC Cabinet Power Switch 
!
CAUTION:
The latch acts as the DC power switch and only removes DC power from 
the cabinet, not AC power. To remove AC power, pull the AC power cord 
from the appliance inlet. See 
Figure 1-9
.
Figure 1-9.
CMC Power Supply
Connect Cabinet Grounds and Other Grounds
The following additional grounding requirements must be met:
The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), 
copper, stranded wire (this is in addition to the ground wire in the AC 
power cord)
Figure Notes
1. Latch
psdmdc RPY 011998
1