Set Up and Calibration Procedures
Relays Set Up Group
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
47
7/08
Relay Type - Deviation
Setting up a relay to alarm (energize) when the motor position deviates 10% (+ or -) from the actuator
setpoint can be set up as follows.
setpoint can be set up as follows.
Set Up Group
Parameter
Value
SET RELAY1
RTYP11
DEV
R11VAL
10.00
R11HL
HI
RTYP12
DEV
R12VAL
-10.00
R12HL
LO
RLY1HY
0.0
The resulting action is shown below.
100%
0%
Closed
-10%
RELAY n
Normally Open
Closed
Open
Motor
Position
Position
Input
50%
+10%