System Maintenance
55
Liebert
®
 MC
Figure 30 EBM small and medium fan, Liebert MC series MCS/MCM
Figure 31 EBM large fan—Liebert MC series MCL
Connect uninsulated drain wires from 
communication cables to ground 
connection (GND) as shown below. 
The drain wires must be tied together 
with cable ties and routed away from 
the high-voltage terminals.
NOTE
If replacing a Ziehl-Abegg fan with an 
EBM fan, the existing ferrule must be 
removed from the end of the wires on 
the communication cable for all fans 
except the last fan. Twist wires 
together before inserting into the 
terminal block.
Example:
Twist RSA-labeled conductor of the 
input cable to RSA-labeled conductor 
of the output cable.
Insert the wires into the properly 
marked terminal on the fan, two
wires per RSA, RSB and GND
terminal as shown in Detail A.
Connect uninsulated drain wires from 
communication cables to ground 
connection (GND) as shown below. 
The drain wires must be tied together 
with cable ties and routed away from 
the high-voltage terminals.
NOTE
If replacing a Ziehl-Abegg fan with 
an EBM fan, the existing ferrule 
must be removed from the end of 
the wires on the communication 
cable for all fans except the last 
fan. Twist wires together before 
inserting into the terminal block.
Example:
Twist RSA-labeled conductor of 
the input cable to RSA-labeled 
conductor of the output cable.
Insert the wires into the properly 
marked terminal on the fan, two
wires per RSA, RSB and GND
terminal as shown in Detail B.