Figure 32 Ziehl-Abegg small, medium and large fan, Liebert MC series MCS, MCM and MCL
9.4
Premium Efficiency Control Board Replacement
9.4.1 Replacement Preparation
1. Verify that the following jumpers are installed on the new board (see Figure 33):
• Jumper at J4 and J6 on Pins 2 and 3.
• Jumper  on  J2.
• Jumper on J5 on Pins 1 and 2.
2. Locate the latest revision of the HMI parameters label, 303847P1, included with new control 
board.