mAI085-MB Actuator Interface Technical Manual   /12 
 
 
Distributive Intelligence 
CMC INDUSTRIAL ELECTRONICS LTD 
 
 
Step  Function 
Action at Interface 
Action at 
Actuator Controller 
 
From the Controller Menu, use the 
GEt function to upload the calibrated 
parameters from controller 1. 
Parameters for 
controller 1 in the 
Interface parameter 
table are overwritten 
with values from the 
actuator controller 
no action 
From the Controller Menu, use the tPL 
function to set the values from controller 
1 as a template 
Parameters for 
controller 1 in the 
Interface parameter 
table are stored in a 
temporary template 
register 
no action 
Using the Factory Values Menu, 
propagate the parameters from 
controller 1 to the remaining controllers 
within the Interface. 
Parameters for 
actuator controllers 1-
100 in the Interface’s 
parameter table are 
overwritten with the 
values from the 
template 
no action 
From the Main Menu, save the values 
using the SAv command.  Performing 
the SAv now insures that the Interface’s 
parameter table will not be lost should 
power need to be cycled during the 
remaining steps. You may perform a 
SAv at any time during system setup. 
Parameters are saved 
to non-volatile memory 
in the Interface 
no action 
From the Main Menu, use the Fnd 
function to locate the remaining 
controllers on the network.  Exit 
calibration mode and confirm that all of 
the installed actuator controllers are 
present on the network.  If installed 
controllers are not present, check field 
address settings and wiring and Fnd 
again until all of the controllers are 
found. 
 
 
 
All active flags are 
cleared, then set for 
those actuator 
controllers located on 
the network; controller 
1 is always set to 
active 
no action