CMC electronic MAI085MB Manuale Utente

Pagina di 50
 
mAI085-MB Actuator Interface Technical Manual   /18 
 
 
Distributive Intelligence 
CMC INDUSTRIAL ELECTRONICS LTD 
 
 
5.3.2  Local Menu 
The local menu allows the configuration of parameters specific to the mAI085-MB. 
 
Display  Function 
Response 
oPn 
Selects the Open/Close mode at startup.  Selecting YES will start the 
interface with the OPEN lamp on.  Selecting no will start the interface 
with the CLOSE lamp on.  The default value is no
YES/no 
oPL 
Selects the open relay output pulse timing.  See “Controlling 
Conveying Systems” for details on output pulse timing.  A value of 0 
disables this function.  The default value is 0. 
 
0-255 
seconds 
CPL 
Selects the close relay output pulse timing.  See “Controlling 
Conveying Systems” for details on output pulse timing.  A value of 0 
disables this function.  The default value is 0. 
0-255 
seconds 
oDL 
Selects the open delay.  This delay allows for a conveying system to 
start before beginning to open any actuators.  The delay starts when 
the OPEN key is pressed.  See “Controlling Conveying Systems” for 
details.  A value of 0 disables this function.  The default value is 0. 
0-255 
seconds 
CDL 
Selects the close delay.  This delay allows for a conveying system to 
purge after closing all actuators.  The delay starts when the last 
actuator has been commanded to close.  See “Controlling Conveying 
Systems” for details.  A value of 0 disables this function.  The default 
value is 0. 
0-255 
seconds 
SPd 
Selects the baud rate for the controller communications network.  
Changing the baud rate without first setting the baud rates for all of 
the field devices will result in lost communication to the field devices.  
The default setting is 19200 baud. 
9600, 1920 
 
 
 
5.3.3  Actuator Controller Menu 
The Actuator Controller Menu allows the configuration of the field actuator controller.  In 
addition this menu allows the setup of internal parameters that affect the open/close timing 
of the actuator controllers.  Additional menu items allow the recall and saving of the 
parameters from the field device on an individual controller basis. 
Provision is made to create a template from a specific controller.  This template can then be 
used to preset any additional controllers.  Using the template/copy system can help speed 
up the configuration process.