mAI085-MB Actuator Interface Technical Manual   /19 
 
 
Distributive Intelligence 
CMC INDUSTRIAL ELECTRONICS LTD 
 
 
A menu selection allows the remote calibration of the field actuator controllers.  This function 
sets the field controller into calibration mode and alerts the operator when the calibration is 
complete. 
Before this menu can be entered, the specific controller to be configured must be selected.  
When entering this menu the upper display will show C 0, indicating controller address 0.  
Use the upper arrow keys to select the controller to be configured.  Selecting YES with the 
lower arrow keys enters the configuration menu for the controller shown in the upper display. 
 
Display  Function 
Response 
ACt 
Controller is active and present on the network.  This flag is set 
automatically when the Fnd function is executed.  The network can 
be manually configured using this menu item.  The default setting is 
no, not on the network except for address 1, which is YES
YES/no 
id 
Selects the Identification shown in the upper display for this actuator 
during normal operation.  The numbers 0-9 and all 26 letters of the 
alphabet are represented in the character table.  Some character 
renditions are compromises due to the nature of the 7 segment 
display.  In addition, the -,_ and blank characters are included.  The 
default setting starts with 1 for address 1. 
0-9             
A-Z                  
- _ blank 
SPt 
Sets the default setpoint for this actuator on startup.  Values from 0 
to full scale are permitted. 
0-FS 
odL 
Sets the open delay time for this controller.  When set, this timer 
delays the opening of the actuator.  The delay starts after the open 
delay specified in the Local Menu.  This timer can be used to insure 
accurate blending of materials occurs during conveying system 
startup.  A value of 0 disables this function.  The default value is 0. 
0-255 
seconds 
CdL 
Sets the close delay time for this controller.  When set, this timer 
delays the closing of the actuator.  The delay starts when the CLOSE 
key is pressed.  This timer can be used to insure accurate blending of 
materials occurs during conveying system shutdown.  A value of 0 
disables this function.  The default value is 0. 
0-255 
seconds 
CpY 
Copy the template values to this controller.  The template can be 
loaded from any selected controller using the tPL menu item.  
Selecting YES copies the template values to this controller and the 
menu display returns to Act.  This function will not operate until a 
template has been set. 
YES/no 
tPL 
Set the template using this controller.  Selecting YES copies this 
controllers parameters to the template.  The menu display returns to 
ACt. 
 
YES/no