CMC electronic MAI085MB Manuale Utente

Pagina di 50
 
mAI085-MB Actuator Interface Technical Manual   /23 
 
 
Distributive Intelligence 
CMC INDUSTRIAL ELECTRONICS LTD 
 
 
5.3.6  Diagnostics Menu 
The mTI085 has a built in diagnostics system. This menu allows for the diagnosis of the 
input ports, communications ports and keyboard. Test connectors are required to test the 
communications port. Press the SETUP key to exit any of the diagnostic tests. 
Display  Function 
Response 
io 
Tests the supervisory inputs and outputs. Once selected, energizing 
a supervisory input will close the corresponding supervisory output, 
i.e. energizing input closes output 1. 
rUn 
tP1 
Test communications port 1. A loopback test connector that connects 
pins 2 to 3 and pins 7 to 8 is required. If the test returns a 1 or 2 
response, the RTS/CTS signals are not functioning. If the response is 
10 – 27 the unit is unable to send or receive characters. 
Error 
message, 
GOOd or 
bAd 
tP2 
Test communications port 2. A loopback test connector that connects 
pins 2 to 3 and pins 7 to 8 is required. If the test returns a 1 or 2 
response, the RTS/CTS signals are not functioning. If the response is 
10 – 27 the unit is unable to send or receive characters. 
Error 
message, 
GOOd or 
bAd 
kYb 
Once selected, each press of a keyboard key will return a numeric 
code. Pressing the SETUP key exits the test and does not display a 
code. 
n/a