mAI085-MB Actuator Interface Technical Manual   /21 
 
 
Distributive Intelligence 
CMC INDUSTRIAL ELECTRONICS LTD 
 
 
Display  Function 
Response 
This function will modify the actuator controllers saved 
parameters.  Verify that the calibration sequence completed 
successfully and that the actuator is operating properly before 
placing the field device into service. Actuator controllers that do 
not complete the calibration sequence revert automatically to 
the pre-calibration parameter table saved in the actuator 
controller.
 
*************************************************************************** 
OFt - 
CSP 
Allows the adjustment of the field parameters of the actuator 
controllers.  The descriptions of these parameters are listing in the 
Technical Manual for the mAC/GP1X5-MB actuator controllers and 
gate positioners.  Refer to the mAC/GP1X5-MB Technical Manual for 
further information. 
See 
mAC/GP1X5
-MB 
Technical 
Manual 
 
5.3.4  Modbus Interface Menu 
The Actuator Interface allow remote operation and monitoring over a Modbus network.  
Modbus is an industry standard network protocol for connecting PLC and field devices.  The 
Actuator Controller is a Modbus Slave device and only utilizes the RTU protocol.  See “Using 
the Modbus Network Interface” for further information. 
Display  Function 
Response 
Adr 
Selects the Modbus slave address.  The default address is 1. 
1-125 
SPd 
Sets the baud rate of the Modbus serial port.  The default baud rate 
is 9600 baud. 
300,600, 
1200,2400, 
4800,9600, 
1920 
Par 
Selects whether parity is active on the serial port.  The default is no 
parity. 
YES/no 
 
Odd 
Select the type of parity, even or odd.  A YES response selects odd 
parity, a no response selects even parity.  The default is even parity if 
parity has been enabled. 
YES/no 
 
Prt 
Port Reset Timer; should the Modbus port become disabled due to 
electrical disturbance.  This timer will automatically restart the 
Modbus Slave port; the timer will reset the port at the entered interval 
(in seconds) if no valid Modbus messages are received.  A setting of 
0 disables this function. 
0-255