7.  Controlling Conveying Systems 
The mAI085-MB Actuator Interface allows the direct control of simple conveying systems.  The 
interface has several timers that facilitate this control.  These timers in conjunction with the 
discrete output system control the conveying system.  The following timers are used: 
 
ID 
Description 
Menu 
oPL 
Provides a pulsed output from Output 1 to start a conveying system.  If this 
value is set to 0, Output 1 will remain on continuously whenever the OPEN 
lamp is on.  If a value is set in this timer the output will pulse on for the time 
selected in seconds each time the OPEN lamp turns on. 
LoC 
cPL 
Provides a pulsed output from Output 2 to stop a conveying system.  If this 
value is set to 0, Output 2 will remain on continuously whenever the CLOSE 
lamp is on.  If a value is set in this timer the output will pulse on for the time 
selected in seconds each time the CLOSE lamp turns on.  The operation of 
the output will be delayed if a value is entered into the cdL timer. 
LoC 
odL 
Delays the opening of the actuators to allow the conveying system to fully 
start.  Output 1 will energize (or pulse if oPL is set) immediately upon the 
OPEN lamp illuminating.  The actuators will begin to open after this delay in 
seconds. This timer starts immediately upon entering Open mode. 
LoC 
cdL 
Delays the stopping of the conveying system until all of the gates are closed 
and the system has been purged.  This timer starts after the CLOSE lamp 
illuminates and all of the gates have been issued close commands.  Once 
this timer expires, Output 2 will energize (or pulse if cPL is set).  
LoC 
odL 
This timer allows for the different location of each actuator along a conveying 
system.  Actuators near the start of the conveying system must open first, 
with each successive actuator opening a short time latter.  This ensures an 
accurate blend of the material.  Each actuator has a timer that delays the 
opening after the primary delay odL has expired. 
CtL 
cdL 
This timer allows for the different location of each actuator along a conveying 
system.  Actuators near the start of the conveying system must close first, 
with each successive actuator closing a short time latter.  This ensures an 
accurate blend of the material.  Each actuator has a timer that delays the 
closing when the interface enters Close mode. 
CtL