Toshiba Remote Starter ME00070B Manuale Utente

Pagina di 32
 
PROGRAMMING 
TMS7 SERIES 
ME00070B 
19 
Adjustment: Function 3 Minimum Current and Function 4 Start 
Ramp Time are used together to activate and control the Ramp 
Start mode. 
If the Ramp Start mode is required, set the Minimum Current so 
that the motor begins to accelerate immediately a start is 
initiated. Ramp Start mode is not required, set the Minimum 
Current
 equal to the Current Limit. 
Ramp Start mode should be considered in preference to Current 
Limit start mode in applications where: 
• 
Required start torque can vary from start to start. For 
example conveyors may start loaded or unloaded. In this 
case set Function 3 Minimum Current to a level that will 
start motor in the light load condition and Function 2 
Current Limit to a level that will start the motor in the high 
load condition. 
• 
Starting time of an easily broken away load needs to be 
extended, for example pumps. 
• 
A generator set supply is limited and a slower application 
of load will allow greater time for the generator set to 
respond. 
 
4. 
Start Ramp Time 
Range: 1 – 30 Seconds 
Default Setting: 1 Second 
Description: Sets the ramp time for the Current Ramp start 
mode. 
Adjustment: Set the Start Ramp Time to optimise start 
performance. 
 
5. 
Stop Ramp Time 
Range: 0 – 100 Seconds 
Default Setting: 0 Second (Off) 
Description: Sets the soft stop ramp time for soft stopping of 
the motor. 
Adjustment: Set the Stop Ramp Time to produce the desired 
motor stopping performance. 
Two soft stop modes are provided by the TMS7. Use Function 
10. Soft Stop Mode to select the desired mode. 
If utilising the Soft Stop function and a line contactor, the 
contactor must not be opened until the end of the stop ramp 
time. The TMS7 programmable outputs A,B or C can be set for 
control of the line contactor. Refer Functions 21, 22, 23 for 
programmable output assignment details. 
 
6. 
Motor Trip Class 
Range: 0 – 60 Seconds 
Default Setting: 10 Seconds 
CAUTION
 
NOTE: 
A setting of 0 seconds disables the TMS7 motor 
thermal model. Use this setting only if another form 
of motor protection is used. 
Description: Sets the motor thermal capacity used by the TMS7 
motor thermal model. 
Adjustment: Set the Motor Trip Class (MTC) according to the 
motor’s thermal capacity. 
A motor’s thermal capacity is expressed as the maximum time 
(seconds) a motor can maintain locked rotor current conditions 
from cold, and is often referred to as Maximum Locked Rotor 
Time or Maximum DOL Start Time. This information is available 
from the motor data sheet or direct from the motor supplier. 
CAUTION
 
NOTE: 
The TMS7 motor thermal model assumes a 
locked rotor current of 600%. If the connected 
motor’s locked rotor current differs from this, 
greater accuracy can be achieved by using a 
normalised MTC figure. A normalised MTC 
figure can be calculated as follows: 
Time
 
Start
Max 
 
X
2
600
%LRC
 
=
 
MTC
 
CAUTION
 
NOTE: 
Setting Function 6 Motor Trip Class according 
to the motor’s actual thermal capacity allows 
safe use of the motor’s full overload capability 
both to start the load and ride through overload 
conditions. Additionally, a more conservative 
approach can be taken by setting a reduced 
MTC for easy to start loads that will not 
experience transient operating overloads as a 
part of normal operation. 
Using a reduced MTC figure has the advantage 
of maximising motor life. The life of a motor is 
strongly influenced by its maximum winding 
temperature, with a 'rule of thumb' stating that 
the expected life span of a motor is halved for 
every ten degree rise in temperature. The 
temperature rise is dependent on the motor 
losses and the motor cooling. The highest 
stress on the motor is during start, and can be 
minimised by restricting the duration and 
frequency of starts. A reduced MTC setting 
(Function 6) will also cause the TMS7 
protection to operate before the motor is 
thermally stressed. 
A suitable reduced MTC figure can be 
established by observing the modeled motor 
temperature as shown on the TMS7 LED 
display, and adjusting the MTC parameter such 
that after a normal start which has been 
preceded by a period of running at maximum 
load, the calculated motor temperature is 
approaching 90%. 
Cold start curves
1
10
100
1000
10000
100
300
500
700
I (% FLC)
t(s)
MTC = 5 Sec
MTC = 10 Sec
MTC = 20 Sec
MTC = 30 Sec