PROGRAMMING 
 
20 
ME00070B 
TMS7 SERIES 
7. 
Current Imbalance Sensitivity 
Range: 1 – 10 
1 = Highest sensitivity (lowest imbalance) 
5 = Average sensitivity  
10 = Lowest sensitivity (highest imbalance) 
 
Default Setting: 5 
Description: Sets the sensitivity of the current imbalance 
protection. 
Adjustment: The factory setting is suitable for most applications 
however the sensitivity can be adjusted to accommodate site 
specific tolerances 
 
8. 
Undercurrent Protection 
Range: 15% – 100% FLC 
Default Setting: 20% FLC 
Description: Sets the trip point for the TMS7 undercurrent 
protection as a percentage of motor full load current. 
Adjustment: Set to a level below the motors normal working 
range and above the motor’s magnetising (no load) current. 
To disable the undercurrent protection make a setting less than 
the magneti sing current of the motor, typically 25% - 35% of 
rated Full Load Current. 
CAUTION
 
NOTE: 
Undercurrent protection is only operative during 
‘run’. 
 
9. 
Stall Protection 
Range: 80% – 550% FLC 
Default Setting: 400% FLC 
Description: Sets the trip point for the TMS7 stall protection as 
a percentage of motor full load current. 
Adjustment: Set as required. 
 
CAUTION
 
NOTE: 
Stall protection is operative only during ‘run’. 
 
10. 
Soft Stop Mode 
Range: 0 – 1 
0 = Standard soft stop 
1 = Pump control 
Default Setting: 0 (Standard soft stop) 
Description: Sets the active soft stop mode. 
Adjustment: The standard soft stop mode automatically 
monitors motor deceleration and will provide optimum control for 
most applications. Pump control may however offer superior 
performance in some applications and can be of particular 
benefit in some pumping applications. 
 
20. 
Local/Remote Operation
 
Range: 0 – 3 
0 = TMS7 Local/Remote push button always enabled. 
1 = TMS7 Local/Remote push button disabled while motor 
running. 
2 = Local control only. (TMS7 push buttons enabled, remote 
inputs disabled) 
3 = Remote control only. (TMS7 push buttons disabled, remote 
inputs enabled) 
Default Setting: 0 (Local/Remote button enabled) 
Description: Enables and disables the local push buttons and 
remote control inputs. Also determines when and if the 
Local/Remote push button can be used to switch between local 
and remote control. 
Adjustment: Set as required 
 
21. 
Relay Output A Functionality 
Range: 0 –11 
0 = Tripped 
1 = Overcurrent trip 
2 = Undercurrent trip 
3 = Motor thermistor trip 
4 = Starter overtemperature trip 
5 = Phase imbalance trip 
6 = Electronic shearpin trip 
7 = Low current alarm 
8 = High current alarm 
9 = Motor overload alarm 
10 = Start/Run 
11 = Main contactor. 
Start signal
Output voltage
RELAY FUNCTIONS
Main contactor
Start/Run
Run
Pre-start Tests
 
Default Setting: 11 (Main Contactor) 
Description: Assigns the functionality of programmable relay 
output A. 
Adjustment: Set as required 
 
22. 
Relay Output B Functionality 
Range: 0 - 11 
Default Setting: 10 (Start/Run) 
Description: Assigns the functionality of programmable relay 
output B. 
Adjustment: Refer Function 21 Relay Output A Functionality for 
adjustment detail. 
 
23. 
Relay Output C Functionality 
Range: 0 - 11 
Default Setting: 0 (Tripped) 
Description: Assigns the functionality of programmable relay 
output C.