Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
132
Sterilization 
The output CVn OV is a “kill time”, F
0
, which quantifies the destruction of microorganisms during a 
sterilization process. F
0
 represents the number of minutes after which the microorganism population is 
decreased by one decimal or log unit. The F
0
 formula is: 
F
0
 = 
∑  [dt x (10
(T-Tref)/Z
)] 
where: 
dt = time between F
0
 measurements, in minutes.  Dt is equal to the scan cycle of the instrument in 
minutes. 
T = measured temperature input, in °C 
T
ref
 =  reference temperature (121°C typical) 
Z = product-dependent temperature constant 
This function also compares the calculated F
0
 value to the desired F
0
 value, F
d
 (Preset). When F
0
 
equals or exceeds F
d
, the function activates its discrete output CVn OS; this output remains ON(1) until 
the F
0
 calculation is reset via the Reset Input. 
The output CVn A2 is the Time Remaining (Tr) at the current temperature to achieve F
d
 and is 
calculated as follows: 
           (F
d
 – F
0
Tr =  
_________
 
           10
(T-Tref)/Z
 
The F
0
 calculation will be reset and the F
0
 value will remain at zero while the Reset Input is ON(1). The 
calculation will resume when the Reset Input goes OFF(0) again. 
Table 4-40 describes the Sterilization prompts. See Table 4-2 for additional prompts. 
Table 4-40   F
0
 Sterilization Prompts 
 
 
Prompt 
Range/Selections 
Definition 
OUT LOW LIMIT 
OUT HIGH LIMIT 
OFF or number 
Displayed output value will be clamped and will flash 
when these limits are exceeded. 
RESET 
OFF, discrete parameter, 0, 
Reset input 
TEMP INPUT 
OFF, analog parameter, 
number 
Measured temperature in degrees C 
REFERENCE TEMP 
OFF, analog parameter, 
number 
Reference temperature 
TEMP CONSTANT 
OFF, analog parameter, 
number 
Temperature constant Z 
DESIRED F0 
OFF, analog parameter, 
number 
Desired F
0
 (F
d