Honeywell VRX180 Manuale Utente

Pagina di 294
Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
134
 
Table 4-41 Advanced Splitter Prompts 
 
 
Prompt 
Range/Selections 
Definition 
RANGE LOW 
RANGE HIGH 
OFF or number 
Enter the output's display limits. Output is not clamped or 
flashed when it exceeds these limits. 
INPUT 
OFF, analog parameter, 
number 
Input source.  Typically, this is the output value (OV) of a 
Split Output type of loop. 
FEEDBACK #1 
OFF, AOn BC, LPn BC 
Select the back calculation value (BC) of the analog output 
assigned to the A1, A2, and A3 outputs, respectively. 
FEEDBACK #2 
 
 
FEEDBACK #3 
 
 
OUT#1 IN LO LIM 
OUT#1 IN HI LIM 
OFF or number 
Enter a range for A1's input. Defauts are 0 for low limit & 30 
for high limit. When input is between these values, A1 
output is scaled between OUT#1 OUT LO LIM & OUT#2 
OUT HI LIM. 
OUT#1 OUT LO LIM 
OUT#1 OUT HI LIM 
OFF or number 
Enter OFF or a range for A1’s output.  Defaults are 0 for low 
limit & 100 for high limit.  Scales A1 output. 
OUT#2 IN LO LIM 
OUT#2 IN HI LIM 
OFF or number 
Enter a range for A2’s input.  Defaults are 30 for low limit & 
60 for high limit.  When input is between these values, A2 
output is scaled between OUT#2 OUT LO LIM & OUT#2 
OUT HI LIM. 
OUT#2 OUT LO LIM 
OUT#2 OUT HI LIM 
OFF or number 
Enter OFF or a range for A2’s output.  Defaults are 0 for low 
limit & 100 for high limit.  Scales A2 output. 
OUT#3 IN LO LIM 
OUT#3 IN HI LIM 
OFF or number 
Enter a range for A3’s input.  Defaults are 60 for low limit & 
90 for high limit.  When input is between these values, A3 
output is scaled between OUT#3 OUT LO LIM & OUT#3 
OUT HI LIM. 
OUT#3 OUT LO LIM 
OUT#3 OUT HI LIM 
OFF or number 
Enter OFF or a range for A3’s output.  Defaults are 0 for low 
limit & 100 for high limit.  Scales A3 output.