Programming Function Blocks and Features  
 
Video Recorder – User Manual 
 
141
CEMS Block Average 
Outputs a block mean average CVn OV over the specified Average Period.  The average is calculated 
from input samples taken at equally spaced Sample Periods.  All samples are discarded at the end of 
the Average Period and the Average Period begins again. 
Samples are ignored when Calibrate Hold is ON(1).  After the Average Period the new average is 
calculated using only the samples taken before and after the Hold.  If no valid samples are taken, the 
output maintains its previous value. 
Table 4-48 describes the CEMS Block Average prompts. See Table 4-2 for additional prompts. 
Table 4-48   CEMS Block Average Prompts 
 
 
Prompt 
Range/Selections 
Definition 
RANGE LOW 
RANGE HIGH 
OFF or number 
Enter the output’s display limits.  Output is not clamped or 
flashed when it exceeds these limits. 
INPUT 
OFF, analog parameter, number 
Input to be averaged 
RESET 
OFF, discrete parameter, 0, 1 
When discrete is ON(1), average is reset to zero; when 
ON(1)-to-OFF(0), average restarts. 
TIME UNITS 
SECONDS, MINUTES, HOURS, 
or DAYS. 
Time units of the averaging period 
AVERAGE PERIOD 
OFF or number 
Number of time units per average period. 
SAMPLE PERIOD 
OFF or number 
Number of time units between samples.  Must divide 
evenly into Average Period. 
CALIBRATE HOLD 
OFF, discrete parameter, 0, 1 
When ON(1), no samples are taken and the output is held. 
CEMS Rolling Average (CEM Rolling Avg)  
Outputs a rolling mean average CVn OV over the specified Average Period.  Average is updated every 
Frame Period thereafter.  Samples are taken at every scan cycle of the instrument, except when 
Calibrate Hold is ON(1). 
Frame Period
Average Period
Inp ut
Time between  samples  = 1 machine  scan cycle
First average  
Second average  
Third average  
 
Figure 4-15   CEMS Rolling Average 
Table 4-49 describes the CEMS Rolling Average prompts. See Table 4-2 for additional prompts.