Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
142
Table 4-49   CEMS Rolling Average Prompts 
 
 
Prompt 
Range/Selections 
Definition 
RANGE LOW 
RANGE HIGH 
OFF or number 
Enter the output’s display limits.  Output is not clamped or flashed 
when it exceeds these limits. 
INPUT OFF, 
analog 
parameter, number 
Input to be averaged. 
RESET OFF, 
discrete 
parameter, 0, 1 
When discrete is ON(1), average is reset to zero; when ON(1)-to-
OFF(0), average restarts. 
TIME UNITS 
Seconds, minutes, 
hours, or days. 
Time units of the averaging period. 
AVERAGE PERIOD 
OFF or number 
Number of time units per average period. 
FRAME PERIOD 
OFF or number 
Number of time units per Frame Period.  Must divide evenly into 
Average Period. 
CALIBRATE HOLD 
OFF, discrete 
parameter, 0, 1 
When ON(1), no samples are taken and the output is held. 
If calibrate hold is set ON, the function block stops acquiring 
samples; however, the averaging will continue to update for the 
remainder of the average period, after which, the output value will 
hold. 
If calibrate hold is set ON longer than the average period, the 
display will alternate between the last output value and 
*****(indicating the current value is no longer valid). 
If calibrate hold is set OFF and the CEM Rolling Average is not 
reset
, the CEM Rolling Average will continue to update every frame 
period from the last value. If the CEM Rolling Average is reset, the 
average value is set to zero and the displayed value will not update 
until the Average period has transpired. The average value will 
update every frame period.